联
Product details
AD80 Vertor Inverter for general purpose
Product Features
1、Plenty of Functions for General Purpose
With V/F and vector control;
Rich lO terminals and functions ;
Rich application functions, including process closed loop and multi-stage speed control etc.
2、Pluggable Keypad
Keypad hot-pluggable and can be remoted
Incremental potential meter.
3、Book Style Compact Size
Latest technology ofIGBT Chip with low switching power loss and high junction temperature rating.
Optimized in structure design and intelligent heat-temperature management to achieve the compact size and best power density.
Book style dimensions, supporting side-by-side mounting to save space in the cabinet.
4、High Reliability in Harsh Environment
Dust proof: fully sealed frame and electronics isolated from forced cooling air
Humidity proof: Coated PCBAs and specialized PCB layout and construction to counter humidity.
High temperature: Nominal load for 45°C ambient temperature, operation upto 60°C ambient.
Wide grid voltage range: 220V -15%~260V +10%,380V -15%~480V +10%
5、Easy to use
High motor control performance can be achieved without setting complex parameters.
Screw-free terminal for quick wiring
6、High performance cost ratio
Product Specifications

Number | Model | Description |
1 | AD80 | On behalf of the inverter AD 80 series |
2 | 4T | Represents the voltage level, 4T: three-phase 380V 2T: three-phase 220V 2S: single-phase 220V |
3 | 1D5 | Represents the power level, 1D5 represents 1.5kW |
AD80 product model specifications:
Model | Power(kW) | Voltage(V) | Input current(A) | Output current(A) | Air(m3/h) |
AD80-2SD37 | 0.37 | 1×200-240 | 6.2 | 2.2 | 17.2 |
AD80-2SD75 | 0.75 | 1×200-240 | 9 | 4.2 | 17.2 |
AD80-2S1D5 | 1.5 | 1×200-240 | 15 | 6.8 | 17.2 |
AD80-2S2D2 | 2.2 | 1×200-240 | 22.5 | 9.2 | 17.2 |
AD80-4TD75 | 0.75 | 3×380-440 | 3.6 | 2.2 | 17.2 |
3×440-480 | 3.1 | 2.0 | |||
AD80-4T1D5 | 1.5 | 3×380-440 | 5.9 | 3.7 | 17.2 |
3×440-480 | 5.1 | 3.4 | |||
AD80-4T2D2 | 2.2 | 3×380-440 | 8.3 | 5.1 | 17.2 |
3×440-480 | 7.3 | 4.8 | |||
AD80-4T4D0 | 4.0 | 3×380-440 | 14.6 | 9.2 | 45.5 |
3×440-480 | 12.6 | 8.4 | |||
AD80-4T5D5 | 5.5 | 3×380-440 | 19.2 | 12.0 | 90 |
3×440-480 | 18.0 | 10.9 | |||
AD80-4T7D5 | 7.5 | 3×380-440 | 24.7 | 15.5 | 90 |
3×440-480 | 21.4 | 14.2 | |||
AD80-4T011 | 11 | 3×380-440 | 35.9 | 25 | 124 |
3×440-480 | 31.4 | 22.7 | |||
AD80-4T015 | 15 | 3×380-440 | 43.4 | 32 | 170 |
3×440-480 | 40.2 | 29.1 | |||
AD80-4T18D | 18.5 | 3×380-440 | 51.5 | 38 | 230 |
3×440-480 | 46.1 | 34.5 | |||
AD80-4T022 | 22 | 3×380-440 | 61 | 45 | 272 |
3×440-480 | 54.5 | 40.9 | |||
AD80-4T030 | 30 | 3×380-440 | 82.5 | 61 | 303 |
3×440-480 | 74 | 52 | |||
AD80-4T037 | 37 | 3×380-440 | 115 | 73 | 374 |
3×440-480 | 103 | 65 | |||
AD80-4T045 | 45 | 3×380-440 | 133 | 88 | 408 |
3×440-480 | 120 | 79 | |||
AD80-4T055 | 5 | 3×380-440 | 150 | 105 | 476 |
3×440-480 | 142 | 97 | |||
AD80-4T075 | 7 | 3×380-440 | 200 | 145 | 595 |
3×440-480 | 180 | 130 | |||
AD80-4T090 | 90 | 3×380-440 | 233 | 172 | 646 |
3×440-480 | 210 | 155 | |||
AD80-4T110 | 110 | 3×380-440 | 273 | 204 | 714 |
3×440-480 | 245 | 187 | |||
AD80-4T132 | 132 | 3×380-440 | 320 | 250 | 850 |
3×440-480 | 288 | 225 | |||
AD80-4T160 | 160 | 3×380-440 | 375 | 302 | 1029 |
3×440-480 | 336 | 272 | |||
AD80-4T185 | 185 | 3×380-440 | 430 | 350 | 1190 |
3×440-480 | 388 | 315 |
Product Specifications:
Project | Specification | ||
Input | Voltage | Single phase 200~240V - 15%~+10% 3-phase 380~480V - 15%~+10% | |
Frequency | 50/60Hz ± 5% | ||
Maximum unbalance degree | 3% | ||
Output | Output voltage | 3-phase 0~100% output voltage | |
Output frequency | 0~590Hz | ||
Main control Specifications | Control mode | V/F, Vector control | |
Supported motor types | Asynchronous motor; synchronous motor | ||
Starting torque | 0.5Hz 150% | ||
Overload capacity | 150 % rated output current (60s) ; 180% rated output current (3s) | ||
Carrier frequency | 0.37kW~7.5kW:2~12kHz;11kW~30kW:2~8kHz 37kW~110kW:2~6kHz;132kW~185kW:2~4kHz | ||
Speed setting resolution | Digital: 0.001Hz, Analog: 0.5‰ of the maximum operating frequency | ||
Open loop speed control accuracy | ±0.5% rated | ||
Control source of the command | Keypad,Communication,Digital input | ||
Set frequency source | Keypad,Analog input, Communication | ||
Acc / Dec | 4 Groups Paraineter for Acc/Dec ; 0.05-60 00.00s | ||
Basic function | Speed open loop, process closed loop control , AMA, automatic load compensation, DC compensation, acceleration and deceleration curve control, DC braking, AC braking, speed limit, current limit, fly start, etc. | ||
Application function | End-controlled multi-stage speed, programmable multi-stage speed, S ramp, mechanical brake, counter, process PID , point control and so on. | ||
Protective function | Short circuit,ground fault,line phase loss,under voltage,over current,overload,over temperature motor thermal protection,motor phase loss,control wire broken etc. | ||
Control terminal | 0.37~30kW | 37kW~185kW | |
| Digital input | 5DI,Select NPN or PNP by Jumper | 5DI,Select NPN or PNP by Jumper | |
| Analog input | 2AI,Select 0~10V/0~20mA by Jumper | 2AI,Select 0~10V/0~20mA by Parameter | |
| Analog output | 1AO,Select voltage or current mode by jumper | 2AO,Select voltage or current mode by jumper | |
| Relay output | 1,Single pole double throw | 2,Single pole double throw+Single pole double throw | |
| Communication port | 1 RS485 | 1 RS485 | |
| Digital output | 1DO of 40mA | 1DO of 40mA | |
| Output power supply | 24V/50mA | 24V/50mA | |
| Analog Reference Power | 10V/30mA | 10V/30mA | |
| Operation keyboard | LED,Hot pluggable | LED,Hot pluggable | |
| External keyboard interface | RJ45,Can be externally connected to KP00 | RJ45,Can be externally connected to KP10 | |
| Environment | Protection grade | IP20 | |
| Working temperature | Operating range -10 °C ~ 55°C 45 ℃ rated load derate from 45 ℃ above | ||
| Working humidity | 5%-95% (no condensation at 95%) | ||
| Vibration | ≤110kW, 1.14g ≥132kW, 0.7g | ||
| Maximum altitude | 3000m, Derate for 1000m abve | ||
| Motor cable length | Shielded cable: 50 meters; Unshielded cable: 100m | ||
| Other | Braking unit | 0.37-30kW built-in brake unit 37~110kW internal brake optional Above 132kW without brake unit | |
Product Size

Power unit casing size table
Frame size | Power and voltage leve | Dimensions(mm) | ||||||
| 1×200-240V | 3×380-480V | W | H | D | W1 | H1 | d |
S0 | 0.37-1.5kW |
| 72 | 170 | 138 | 55 | 160 | 4.5 |
S1 | 2.2kW | 0.75-4.0kW | 82 | 185 | 163 | 65 | 175 | 4.5 |
S2 |
| 5.5-7.5kW | 100 | 250 | 164 | 80 | 240 | 4.5 |
S3 |
| 11-18.5kW | 155 | 330 | 189 | 130 | 315 | 6.5 |
S4 |
| 22kW | 180 | 380 | 189 | 145 | 355 | 6.5 |
| 30kW | 180 | 380 | 223 | 156 | 365 | 6.5 | |
S5 |
| 37-55kW | 240 | 490 | 265 | 180 | 475 | 9 |
S6 |
| 75-110kW | 315 | 660 | 285 | 200 | 640 | 9 |
S7 |
| 132-185kW | 395 | 800 | 310 | 280 | 780 | 13 |
Product Documentation
2023-06-02
2024-07-29
2025-06-06
Message Consultation